Quick answer
LED displays list two power figures, and they do different jobs. Maximum power (for example 300 W/m²) is what the wall can draw showing full white at full brightness; use it to size circuits, cabling, breakers, UPS and generators. Average power (for example 100 W/m²) is what the wall typically draws with normal content; use it to estimate energy cost. The maximum is usually about three times the average. A 20 m² EA640H1 indoor wall therefore needs a supply for about 6 kW, but averages about 2 kW and uses roughly 8,760 kWh a year at 12 hours a day.
Sources used: EA600COB3 specs; EA640H1 specs; EA1000H9 specs; EA640F2 specs
Never size the supply on the average figure: a white slide or a bright scene can draw close to the maximum and trip breakers or overload a generator.

Documented average and maximum power by model
| Model and configuration | Average | Maximum | Ratio |
|---|---|---|---|
| EA600COB3 COB, P0.62 and P0.78 | 50 W/m² | 140 W/m² | 2.8 |
| EA600COB3 COB, P0.93–P1.56 | 95 W/m² | 280 W/m² | 2.9 |
| EA600COB3 COB, P1.87 | 75 W/m² | 220 W/m² | 2.9 |
| EA640H1, all pitches | 100 W/m² | 300 W/m² | 3.0 |
| EA640F2 SMD | 100–110 W/m² | 300–330 W/m² | 3.0 |
| EA640F2 COB | 80–100 W/m² | 230–300 W/m² | 2.9–3.0 |
| EA1000H9 indoor | 100–192 W/m² | 300–576 W/m² | 3.0 |
| EA1000H9 outdoor | 170–240 W/m² | 500–720 W/m² | 2.9–3.0 |
| EA960F4 outdoor | 170 W/m² | 500 W/m² | 2.9 |
| EA960R4 P10 DIP outdoor | 110 W/m² | 330 W/m² | 3.0 |
All four sourced models list AC 100–240 V, 50–60 Hz input. Those are input conditions, not a substitute for the W/m² figures. EagerLED’s EA600COB3 documentation explicitly labels its average figure for running-cost estimates, and the EA1000H9 documentation says to size the generator, distro and cabling on maximum figures rather than averages.
Sizing circuits and cabling from the maximum
Multiply the wall’s active area by the maximum W/m² for the exact model, pitch and indoor or outdoor version, then add the processor, media player and any other equipment on the same supply.
| Example | Area | Maximum load | Current at 230 V single-phase | Per phase at 400 V three-phase | At 120 V single-phase |
|---|---|---|---|---|---|
| EA640H1 indoor wall | 20 m² | 6.0 kW | about 27.5 A | about 9.1 A | about 52.6 A |
| EA1000H9 outdoor rental wall | 30 m² | 21.6 kW | about 99 A | about 32.8 A | — |
Currents assume a power factor of about 0.95. These are planning numbers for the electrician, who chooses the breakers, cable sizes and distribution for the site and the local electrical code. Split large walls across several circuits so one fault does not black out the whole screen, and keep inrush current in mind: switching on many power supplies at once draws a surge, so many installations power cabinets up in groups.
Generators and UPS
For outdoor events and temporary walls, EagerLED’s EA1000H9 documentation is explicit: size the generator, distro and cabling on the maximum figures. A 30 m² outdoor EA1000H9 wall at 720 W/m² needs a generator able to supply about 21.6 kW plus the rest of the video system, with headroom; many engineers add a margin above the maximum so the generator is not run at its limit. The LED screen rental price guide covers what else a hire quote includes.
A UPS for a control room or broadcast wall is sized the same way. It must carry the maximum load for the time needed to ride through a short outage or shut down safely. For 24/7 rooms, see control room LED video wall.
Estimating energy cost from the average
Energy per year = area × average W/m² × hours per day × days per year ÷ 1,000 (in kWh).
| Example | Area | Average | Hours | Energy |
|---|---|---|---|---|
| EA640H1 indoor wall | 20 m² | 100 W/m² = 2.0 kW | 12 h × 365 days | about 8,760 kWh a year |
| EA1000H9 outdoor event wall | 30 m² | 240 W/m² = 7.2 kW | 10 h | about 72 kWh per show day |
Multiply by your tariff to get the cost. Real consumption depends on content and brightness: dark content and dimmed screens use less, bright white content more. Outdoor screens dim at night, which cuts their average considerably. For a full ownership budget, see LED screen running cost, power, spares and shipping.
Surge protection, grounding and power quality
Outdoor screens need surge protection on the incoming supply and proper grounding of the structure and cabinets, because a lightning strike nearby or a fault on the grid can damage power supplies across the whole wall. Indoors, a stable supply matters most for walls that run all day: ask the electrician whether the building’s supply needs conditioning, and keep the screen on circuits separate from motors, lifts or kitchen equipment that cause voltage dips.
On temporary sites, check the generator’s voltage and frequency stability under load before connecting the screen, and switch the screen on after the generator has stabilised. Power the cabinets up in groups rather than all at once to limit the inrush current.
Heat load for air conditioning
Almost all the electrical power a screen draws becomes heat. For indoor walls, give the HVAC designer both figures: the average for the normal cooling load and the maximum for the worst case. A 2 kW average load is about 6,800 BTU/h; a 6 kW maximum about 20,500 BTU/h. In small rooms, such as control rooms or meeting rooms, that is significant.

Read each power table by model, pitch and environment
Power figures change with the exact product, pitch and version:
- Confirm the model and exact configuration, including SMD, GOB or COB.
- Confirm whether the row is for indoor or outdoor use: EA1000H9 indoor and outdoor figures differ.
- Confirm the pitch group: EA600COB3 uses different figures at P0.62–P0.78, P0.93–P1.56 and P1.87.
- Read the maximum for sizing and the average for energy.
EA640F2 shows why configuration matters: its SMD options run 100–110 / 300–330 W/m², while its COB options run 80–100 / 230–300 W/m². If a table shows only one figure, ask which one it is.
Does higher brightness mean higher power?
Usually, but LED type matters. Outdoor screens draw more because they run at 4,500–6,500 cd/m², but the EA960R4 P10 DIP reaches 8,000 cd/m² at only 330 W/m² maximum, against 630 W/m² for the P10 SMD version. Compare the figures for each exact version; see outdoor LED brightness: 4500 vs 5000 vs 6500 nits.
Scenarios and what to confirm
| Scenario | What to confirm |
|---|---|
| Fixed indoor wall | Maximum for the circuit; average for energy; heat load |
| Outdoor billboard | Maximum per face, surge protection, grounding, night dimming schedule |
| Outdoor rental event | Generator and distro sized on maximum, with headroom |
| 24/7 control room | UPS on maximum, cooling on average and maximum |
| Mixed SMD and COB walls | Separate figures for each part of the wall |
For stadium installations with large loads, see stadium LED display cost.
Frequently asked questions
Should I size an LED wall’s power on average or maximum consumption?
Size circuits, cabling, UPS and generators on the maximum. Use the average only for energy cost estimates.
How much power does an LED wall use?
Indoor walls average about 50–110 W/m² and outdoor walls about 170–240 W/m², with maximums about three times higher. A 20 m² indoor wall averages about 2 kW.
Why is maximum power so much higher than average?
Maximum is measured at full white and full brightness; real content is darker and screens are often dimmed, so they draw about a third of the maximum on average.
How big a generator does an outdoor LED screen need?
At least the maximum load of the wall plus the video system, with headroom. A 30 m² EA1000H9 outdoor wall at 720 W/m² needs about 21.6 kW before margin.
Does dimming an LED wall reduce its power use?
Yes. Power falls roughly with brightness and with darker content, which is why outdoor screens that dim at night and indoor screens running well below their rating use much less than the maximum.
How much heat does an LED wall produce?
Nearly all its power. A wall averaging 2 kW adds about 6,800 BTU/h to the room’s cooling load.
Send the wall size, model and site power details to request a quote with a sizing calculation.
Check the details
Sources & references
Source pages can change. Access dates record when they were consulted.
- EA600COB3 specs Accessed 29 October 2026
- EA640H1 specs Accessed 29 October 2026
- EA1000H9 specs Accessed 29 October 2026
- EA640F2 specs Accessed 29 October 2026
Put these details into your project brief.
Tell EagerLED the application, destination and screen dimensions you have in mind.
Request a project quote