Quick answer

Budget the electrical service upgrade as a separate project line from the LED cabinets. Ask for the maximum W/m² of the exact quoted configuration, then have a licensed electrician price panel capacity, feeder, breakers, disconnects, earthing and utility coordination against that load. Keep cabinet and electrical scopes separate so quotes compare like for like; totals are project-specific.

Sources used: EA1000H9 specs; EA640F2 specs; EA1000TiF2 specs

Start With Maximum W/m², Not Average

The electrical upgrade budget starts with the display’s maximum load, not its average. For EA1000TiF2, the published average power consumption is 220 W/m² and maximum power consumption is 800 W/m², and the source says to confirm site ventilation, power capacity, and mounting conditions before installation. For EA1000H9, cabinets run on AC 100-240 V, 50-60 Hz; outdoor models draw 170 to 240 W/m² average and 500 to 720 W/m² maximum, while indoor models draw 100 to 192 W/m² average and 300 to 576 W/m² maximum. For EA640F2, cabinets run on AC 100-240 V, 50-60 Hz; average consumption is 100-110 W/m² for SMD and 80-100 W/m² for COB, while maximum consumption reaches 300-330 W/m² for SMD and 230-300 W/m² for COB.

Ask for the maximum figure for the exact quoted model, pitch and configuration. EA1000H9 evidence says to size the generator, distro and cabling on the maximum figures rather than the averages. EA640F2 evidence says to size the electrical supply and cabling on the maximum figure rather than the average. Use an average vs maximum power method so the sizing basis is visible in the quotation.

Keep the Cabinet Quote and Electrical Upgrade Separate

Treat the LED cabinet quotation and the electrical upgrade as two different scopes. EA1000H9 pricing depends on pixel pitch, screen size, cabinet quantity, control system, spare modules and freight, so every wall is quoted per project. EA640F2 pricing is quoted per project because pixel pitch, cabinet quantity, control equipment, spare parts and delivery all affect the total. Keep hardware vs installed cost separate so the cabinet total does not hide electrical site work. Ask the electrical contractor to price the upgrade as its own scope rather than assuming it sits inside the cabinet line.

Our recommended budgeting method is to ask for an itemised cabinet quotation and a separate written electrical scope. For EA1000H9, request width, height, viewing distance, indoor or outdoor use and delivery city, and ask for an itemised quotation including spares and shipping. Then compare the electrical upgrade on the same screen area, cabinet count and maximum load. Use a compare LED screen quotes checklist so cabinet lines and site lines answer the same rows.

Electrical Upgrade Decisions and Evidence to Request

Decision Evidence to request
Display load input Maximum W/m² for the exact quoted model and configuration. Documented examples: EA1000TiF2 800 W/m² maximum; EA1000H9 indoor 300-576 W/m² maximum and outdoor 500-720 W/m² maximum; EA640F2 SMD 300-330 W/m² maximum and COB 230-300 W/m² maximum.
AC input condition AC input for the quoted cabinets. EA1000H9 and EA640F2 cabinets run on AC 100-240 V, 50-60 Hz.
Sizing basis Confirm whether generator, distro or cabling is sized on maximum rather than average. EA1000H9 says size generator, distro and cabling on maximum; EA640F2 says size electrical supply and cabling on maximum.
Site power capacity For EA1000TiF2, confirm site ventilation, power capacity and mounting conditions before installation.
Panel capacity and feeder Ask the electrician to price the building supply, panel capacity and feeder for the total maximum load. This is a site-specific professional scope.
Breakers, disconnects and earthing Ask the electrician to define overcurrent protection, isolation, disconnects and earthing as separate written lines.
Utility coordination Ask who coordinates the utility connection, timeline and inspections, and price that work as its own line.

What the Electrical Upgrade Budget Should Cover

The electrical upgrade should be priced by a licensed electrician for the actual site. Our recommended separate lines are panel capacity, feeder size, breakers, disconnects, earthing and utility coordination. Treat these as site-specific professional services and request them as separate written lines. Give the electrician the exact model, cabinet quantity, screen area, maximum W/m² and documented AC input so the panel and feeder scope is based on the display configuration rather than a generic allowance.

Do not treat a display’s AC input range as a complete electrical design. EA1000H9 and EA640F2 cabinets run on AC 100-240 V, 50-60 Hz, which is a display condition to pass to the electrician. The EA1000TiF2 source separately says to confirm site power capacity before installation. The upgrade scope still needs to be designed and priced for the building supply, protection and connection method.

A Practical Sequence for Pricing the Upgrade

First, fix the exact model, pitch, cabinet quantity and screen area. Second, request the maximum W/m² and AC input for that configuration. For EA1000TiF2, record 800 W/m² maximum and 220 W/m² average; for EA1000H9, record indoor 300-576 W/m² maximum or outdoor 500-720 W/m² maximum and the AC 100-240 V, 50-60 Hz input; for EA640F2, record SMD 300-330 W/m² maximum or COB 230-300 W/m² maximum and the AC 100-240 V, 50-60 Hz input.

Third, give those figures to the electrician and ask for separate written lines for panel capacity, feeder, breakers, disconnects, earthing and utility coordination. Fourth, compare the cabinet quotation and the electrical upgrade side by side, using the same screen area and cabinet count. Defer approval until the electrician has confirmed the upgrade scope and the supplier has confirmed the maximum load for the exact quoted configuration.

Mistakes That Distort the Electrical Upgrade Budget

One mistake is using average W/m² to size the panel or feeder. EA1000H9 evidence says to size generator, distro and cabling on maximum, and EA640F2 evidence says to size electrical supply and cabling on maximum. Average figures are for different purposes; mixing them into the electrical scope understates the load the electrician must price.

Another mistake is comparing a cabinet-only quote with an electrical-inclusive quote. EA1000H9 and EA640F2 prices are project-specific and depend on factors such as pitch, cabinet quantity, control system, spares, freight and delivery. Keep the cabinet line, electrical upgrade line and any site work separate so a low cabinet total does not hide the electrical scope. If the existing panel capacity is not confirmed, treat the project total as provisional.

A third mistake is applying one model’s power figure to another model or configuration. The documented maximums differ: EA1000TiF2 is 800 W/m², EA1000H9 indoor is 300-576 W/m² and outdoor is 500-720 W/m², and EA640F2 SMD is 300-330 W/m² and COB is 230-300 W/m². Use the exact quoted model and configuration in the electrical brief.

Model Power Inputs for the Electrical Brief

Model and configuration Documented power input Sizing note
EA1000TiF2 Average 220 W/m²; maximum 800 W/m² Confirm site power capacity before installation.
EA1000H9 indoor AC 100-240 V, 50-60 Hz; average 100-192 W/m²; maximum 300-576 W/m² Size generator, distro and cabling on maximum.
EA1000H9 outdoor AC 100-240 V, 50-60 Hz; average 170-240 W/m²; maximum 500-720 W/m² Size generator, distro and cabling on maximum.
EA640F2 SMD AC 100-240 V, 50-60 Hz; average 100-110 W/m²; maximum 300-330 W/m² Size electrical supply and cabling on maximum.
EA640F2 COB AC 100-240 V, 50-60 Hz; average 80-100 W/m²; maximum 230-300 W/m² Size electrical supply and cabling on maximum.

EA1000TiF2 illustrative maximum load

Illustrative calculation: 10 × 800 = 8000 W. Illustrative 10 m² EA1000TiF2 wall area using documented 800 W/m² maximum; actual area and configuration must be confirmed.

Buyer checklist

  • Request the maximum W/m² and AC input for the exact quoted model, pitch and configuration.
  • Ask for an itemised cabinet quotation that states spares and shipping separately from the electrical upgrade.
  • Give the electrician the screen area, cabinet count, maximum W/m² and AC input so panel capacity, feeder, breakers, disconnects, earthing and utility coordination can be priced.
  • Confirm that generator, distro, supply and cabling sizing uses maximum rather than average.
  • Keep cabinet, electrical and other site lines separate when comparing quotes.
  • Defer approval until site power capacity and the electrical upgrade scope are confirmed in writing.

Frequently asked questions

How do I turn maximum W/m² into a load figure for the electrician?

Ask the supplier for the maximum W/m² of the exact quoted configuration, then multiply it by the active screen area. Illustrative example: 10 m² × 800 W/m² = 8,000 W for an EA1000TiF2 configuration, using its documented 800 W/m² maximum. Confirm the actual area and configuration with the supplier before using any figure in an electrical design.

Does the LED cabinet quotation include the electrical service upgrade?

The supplied product pages for EA1000H9 and EA640F2 focus on display power and equipment. Their pricing is project-specific and depends on factors such as pitch, cabinet quantity, control system, spares, freight and delivery. Treat the electrical upgrade as a separate written scope and ask for panel capacity, feeder, breakers, disconnects, earthing and utility coordination as their own lines.

Should I use average or maximum power when the panel is already close to capacity?

Use maximum for the electrical sizing basis. EA1000H9 evidence says to size generator, distro and cabling on maximum rather than average. EA640F2 evidence says to size electrical supply and cabling on the maximum figure rather than the average. Average figures are documented for the named models but are not the sizing basis for those electrical items.

What if the existing panel cannot carry the display load?

Defer the purchase decision until a licensed electrician has priced the required panel capacity, feeder, breakers, disconnects, earthing and utility coordination for the actual site. The supplier’s role is to confirm the maximum W/m² and AC input for the exact quoted configuration; the electrical upgrade scope is a separate professional service.

Can I compare one model’s W/m² figure with another?

No. Documented maximums differ by model and configuration: EA1000TiF2 is 800 W/m², EA1000H9 indoor is 300-576 W/m² and outdoor is 500-720 W/m², and EA640F2 SMD is 300-330 W/m² and COB is 230-300 W/m². Use the exact quoted model and configuration in the electrical brief.

What inputs should I send with the quotation request?

For EA1000H9, the source says to send width, height, viewing distance, indoor or outdoor use and delivery city, and to ask for an itemised quotation including spares and shipping. For electrical budgeting, add the maximum W/m² and AC input for the exact configuration so the electrician can price panel capacity and the feeder.

Share your project requirements to request a quote.

Check the details

Sources & references

Source pages can change. Access dates record when they were consulted.

  1. EA1000H9 specs Accessed 6 October 2026
  2. EA640F2 specs Accessed 5 October 2026
  3. EA1000TiF2 specs Accessed 30 September 2026

Put these details into your project brief.

Tell EagerLED the application, destination and screen dimensions you have in mind.

Request a project quote